PROBABILISTIC SAFETY ANALYSIS OF LOSS OF COMPONENT COOLING WATER SYSTEM (LOCW) INITIATING EVENT FOR 300 MWE PWR NUCLEAR POWER PLANTS (NPPS)

Authors

  • H. M. Z. Arif Pakistan Nuclear Regulatory Authority (PNRA), P. O. Box 1912, Islamabad, Pakistan
  • S. Kanwal Pakistan Nuclear Regulatory Authority (PNRA), P. O. Box 1912, Islamabad, Pakistan
  • U. Habib Pakistan Nuclear Regulatory Authority (PNRA), P. O. Box 1912, Islamabad, Pakistan
  • K. Rehman Pakistan Nuclear Regulatory Authority (PNRA), P. O. Box 1912, Islamabad, Pakistan

Abstract

The probabilistic safety analysis (PSA) is an important tool in ensuring the design safety of a nuclear power plant in relation to potential initiating events that can be caused by random component failures and human errors etc. It estimates the risk in the form of core damage frequency (CDF) and enables us to identify systems for which design improvements or modifications to operational procedures could reduce the probabilities of severe accidents or mitigate their consequences. LOCW initiating event analysis for 300 MWe PWR NPP was evaluated by using small event tree and large fault tree technique. The objective of this analysis was to compare the results of the LOCW initiating event with similar NPPs PSA results. The core damage frequency of LOCW initiating event comes out to be 1.08E-07/yr with total of eleven sequences out of which 06 sequences are leading to Core Damage (CD) state. The failure probabilities of SAF & SMF systems are comes out to be 8.27E-03 & 7.85E-03 respectively. The comparison of results with similar NPPs PSA results showed that the CDF contribution of LOCW is highly sensitive to the initiating event frequency. Similarly it is also observed that the CDF of LOCW event can be improved significantly by taking the credit of SMF after failure of SAF.

References

Nuclear Regulatory Commission, Reactor

Safety Study: An Assessment of Accident

Risks in US Commercial Nuclear Power

Plants, Rep. WASH-1400-MR (NUREG/75-

, Washington, DC (1975).

International Atomic Energy Agency,

Defining initiating events for purposes of

Probabilistic safety assessment IAEATECDOC No. 719, (September, 1993).

Directorate General Reactor Engineering,

Probabilistic Safety Assessment Level-1 of

Chashma Nuclear Power Plant Unit-1.

(December, 2005).

Chashma Nuclear Power Plant Unit-2,

Preliminary Safety Analysis Report Chapter

Probabilistic Safety Assessment and

Severe Accident Analysis. (August, 2005).

Qinshan Nuclear Power Plant, Probabilistic

Safety Assessment Level-1 Report.

R. C. Bertucio, et al., Analysis of Core

Damage Frequency: Surry, Unit 1 Internal

Events, NUREG/CR-4550-Vol.3, Rev.1,

Sandia National Laboratories, 1990.

Common-Cause Failure Parameter

Estimations, NUREG/CR-5497, INEL (1998).

A. Mosleh et al., Procedures for Treating

Common Cause Failures in Safety and

Reliability Studies,NUREG/CR-4780, EPRI

NP-5613, Electric Power Research Institute,

January (1988).